The ETC TGZ-24/250 Amp transformer bushing is used in Pad mounted Transformers, branch boxes, Switch
gear and Ring Main Units.
This bushing is used for fixed entry of medium voltage cables to oil type installations and accepts the termination types ETC DB 24/250amp Dead Break Elbows & ETC DBS 24/250amp Straight Dead Breaks meeting the IEEE standard 386.
Application:
– For oil-insulated (R – temp, hydrocarbon, or silicon) apparatus, including switchgear, transformers and capacitors.
– System voltage up to 24kV
– Continuous current 250A
– For Indoor and outdoor installations